Loading...
HomeMy WebLinkAboutord1987-0591 2 3 4 5 6 7 8 9 10 11 12 13. 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 DRAFT II - 10/15/87 INTRODUCED BY: CONSENT PROPOSED BY: PUBLIC WORKS DATE INTRODUCED: SEPTEMBER ORDINANCE NO.' 87 -59 AN ORDINANCE ESTABLISHING MINIMUM STANDARDS FOR REQUIRED FIRE FLOW FOR FIRE PROTECTION AND AMENDING W.C.C. SECTION 15.16.060 AND ADDING A NEW CHAPTER 15.18 TO THE W.C.C. ENTITLED FIRE FLOW. WHEREAS, the Whatcom County Council has previously adopted the 1982 edition of the Uniform Fire Code; and WHEREAS, Section 10.301(c) of that code sets forth the requirement that an approved water supply capable of supplying required fire flow be provided to premises upon which buildings are to be constructed; and WHEREAS, the standards for minimum fire flow are not specifically set forth in this section; and WHEREAS, the establishment of a more specific fire flow standard will provide better information to the public on the fire flow requirement of the County; and WHEREAS, it is the desire of the Whatcom County Council to provide a reasonable minimum fire flow standard which addresses the general need for providing water supply for fire protection, AND which also recognizes the rural character of many areas of the County, NOW, THEREFORE, BE IT ORDAINED that Chapter 15.16.060 of the Whatcom County Code is hereby amended as follows: 15.16.060 Subsection 10.301(c) amended- -Water for fire flow. Subsection 10.301(c) of the Uniform Fire Code, 1982 Edition, is amended to read as follows: ORDINANCE -1- date drafted 10/15/87 (c) An approved water supply capable of supplying required fire flow for fire protection as set forth in Chapter 15.18 W.C.C. shall be provided to all premises upon which buildings or structures or portions of buildings or structures are hereafter constructed. When 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 any portion of the building or structure protected is in excess of 150 feet from a water supply on a public street or county road there shall be provided, when required by the Deputy Fire Marshal or Building Official, on -site fire flow. WakeP- etl$�ly- ailE7- ifPe- €�9w -8h83� �6- �9ts6P- �ir�eci- l� -�#w� ^. ��.. r' �,-- Wor+l Ea- Di- Peo�or +fl3+krltii�g- (�� €ioi�r��sx� $ aaPerr��F- �i�e- Wl�aheea•- 6etrxt�- F�Pe- Q4aPaka� . Water supply may consist of reservoirs, pressure' tanks, elevator tanks, water mains, or other fixed system capable of supplying the required fire flow, provided that where a public water system water line capable of providing the required fire flow is located within 1500 feet of the property, the water supply for fire flow shall be provided by a water line extension installed in accordance with the rules of the water purveyor; provided further that if the total of the construction cost and other fees for the line extension exceeds by more than 25% the cost of a reservoir meeting the standards of section 15.18.070.B and capable of supplying the required fire flow, the owner shall have the choice of either extending the line or installing a reservoir meeting the standards of this chapter. I�r- sett,ag- kl�e- t�eQt��emer�ke €e•P- �l�e- �'�.re-- €lc►wf- tie• -F�Pe - 1rfa�a�.- e�,��n -- the- $it��it4g &S44a4 a1-- -shall -be- Gci04416644el*- hat►r -- Fife - Flea- AeB; +1aA. enov The location, number and type of fire hydrants connected to. a water supply capable of delivering the required fire flow shall be provided on the public street or on the site of the premises to be protected as required and approved by the Deputy Fire Marshal. All hydrants shall be installed pursuant to the standards set forth in W.C.C. 15.18 and be accessible to the Fire District apparatus by roadways meeting the requirements of Section 10.207. BE IT FURTHER ORDAINED, that a new Chapter 15.18 entitled Fire Flow be added to the Whatcom County Code to read as follows: Section 15.18.010 Purpose & Applicability The purpose of this regulation is to establish minimum standards and requirements for the quantity and duration of flow of water for fire fighting purposes to be provided for new structures and developments in Whatcom Count This chapter shall be applicable to all new struc- tures that require building permits and shall be used to determine the required fire flow for fire protection referenced in Section 10.301(c) of the Uniform Fire Code. Section 15.18.020 Definitions Words or phrases used herein shall have the followin meanings unless otherwise provided in the Uniform Fire Code, as adopted by Whatcom County; A. Compartmentalize - shall mean to divide the aggregate floor area or a structure into smaller components by means of area separation walls per U.B.C. 505(d). B. Dead End Main - shall mean a water main over fifty feet long which is not supplied from both ends. ORDINANCE -2- date drafted. 10/15/87 C. Fire Department - shall mean the fire authority normally responsible for fire protection in the area. D. Fire Flow - shall mean the flow of water at 20 .s.i. for specified period of time required to be available for use in extinguishing a fire at a 1 specific building or development. 2 E. Fire Wdrant - ,shall mean a permanently installed mec anica evice by which water is made available to 3 fire apparatus operated by a fire department. 4 F. Fire Marshal - shall mean the Director of the Whatcom County c Works Department, or his designee. 5 G. Fire Resistive Construction - shall mean Type I fire 6 resistive structures an Type II fire resistive structures as defined in the Uniform Building Code. 7 H. Flush Type Hydrant - shall mean a fire hydrant 8 ns a e en re y elow grade. 9 I. G.P.M. - shall mean gallons per minute. 10 J. I.S.O - shall mean Insurance Services Office Pamphlet ent3Nled "Guide for Determination of Required Fire 11 Flow," 1974 Edition. 12 K. Non Combustible Construction - shall mean Type II -N an pe II one-hour s ruc ures as defined in the 13. Uniform Building Code. 14 L. Ordinary Construction - shall mean Type III one -hour, pe Type VI H.T. and Type V one -hour struc- 15 tures as defined in the Uniform Building Code. 16 M. Substantial Alteration - shall mean an alteration to a structure w ere the value of the labor and ma- 17 terials is together more than 40% of the value of the original structure immediately prior to the alter - 18 ation. The value of the structure and of the alteration shall be established by the Building 19 Official who shall be guided by the building valu- ation data contained in the most current October 20 issue of the 'Building Standards ", the official magazine of the International Conference of Building 21 Officials. Substantial alterations shall also mean addition(s) to a structure regardless of va]U a which 22 singly or together increase the gross floor area-of the structure by an amount equal to or greater than 23 10% or which add 500 square feet or more to the gross area of the structure. 24 N. Water Supply - shall mean the source, treatment, 25 rans�and distribution facilities as required to provide water for normal peak consumption and fire 26 flow with residual pressure at the service or fire hydrant in excess of 20 p.s.i. 27 0. Wood Frame Construction shall mean Type V -N 28 structures as defined in the Uniform Building Code. 29 Section 15.18.0 30 Fire Flow Standards 30 Tables 1 through 4 together with any other applicable 31 provisions contained herein shall be used to determine 32 ORDINANCE -3- date drafted 10/15/87 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 the amount of fire flow in gallons per minute required for new construction subject to the provisions of this chapter. Not withstanding any other provisions contained herein the minimum required fire flow for all new construction not exempted from these standards, shall be 500 gpm. Water for fire flow purposes shall be provided at a minimum of 20 psi .pressure and shall be available in an amount sufficient to provide the required fire flow for a duration of one hour, provided that for industrial uses in areas zoned heavy impact industrial the duration shall be two hours. To use the tables first determine the ground area of the structure, the number of stories and the type of con- struction. Using the table corresponding to the type of construction find the column which corresponds to the number of stories of the structure. Select the ap- propriate ground area range corresponding to the ground area of the structure, from the ranges listed in the column and read the fire flow value which corresponds to that ground area range, from the list of values in the lefthand column marked gpm. Ground area shall be the same as the first story floor area computed using Uniform Building Code Standards and Definitions. Number of stories shall be the same as that computed using the Uniform Building Code Standards and Definitions. For the purpose of computing ground area, wood frame structures separated by less than 10 feet shall be considered one structure. ORDINANCE -4- date drafted 10/15/87 1 2 3 4 5 6 7 8 9 10 11 12 13. 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 TABLE 1 FIRE FLOW Wood Frame Construction (ground area in square feet) 500 < - - -- 563 < - - -- 6,200 - - -- 3,100 - - -- 2,100 - - -- 1,600 - - -- 1,200 - - -- 1,000 625 < - - -- 7.700 - - -- 3,900 - - -- 2,600 - - -- 1,900 - - -- 1,500 - - -- 1,300 688 < - - -- 9,400 - - -- 4,700 - - -- 3,100 - - -- 2,400 - - -- 1,900 - - -- 1,600 750 < - - -- 11.300 - - -- 5,700 - - -- 3,800 - - -- 2,800 - - -- 2,300 - - -- 1,900 813 < - - -- 13.400 - - -- 6,700 - - -- 4,500 - - -- 3,400 - - -- 2,700 - - -- 2,200 875 < - - -- 15.600 - - -- 7,800 - - -- 5,200 - - -- 3,900 - - -- 3,100 - - -- 2,600 938 < - - -- 18.000 - - -- 9,000 - - -- 6,000 - - -- 4,500 - - -- 3,600 - - -- 3,000 1000 < - - -- 20,600 - - -- 10,300 - - -- 6,900 - - -- 5,200 - - -- 4,100 - - -- 3,400 1063 < - - -- 23,300 - - -- 11,700 - - -- 7,800 - - -- 5,800 - - -- 4,700 - - -- 3,900 1125 < - - -- 26.300 - - -- 13,200 - - -- 8,800 - - -- 6,600 - - -- 5,300 - - -- 4,400 1188 < - - -- 29,300 - - -- 14,700 - - -- 9,800 - - -- 7,300 - - -- 5,900 - - -- 4,900 1250 <---- 32,600 - - -- 16,300 - - -- 10,900 - - -- 8,200 - - -- 6,500 - - -- 5,400 1313 < - - -- 36,000 - - -- 18,000 - - -- 12,000 - - -- 9,000 - - -- 7,200 - - -- 6,000 1375 < - - -- 39,600 - - -- 19,800 - - -- 13,200 - - -- 9,900 - - -- 7,900 - - -- 6,600 1438 < 43,400 - - -- 21,700 - - -- 14,500 - - -- 10,900 - - -- 8,700 - - -- 7,200 - - -- ll7 llnn____7a 7nn____ir Ann onn____ o Gnn____ 7 nnn 1625 < - - -- 1688 < - - -- 1750 < - - -- 1813 < - - -- 187F C - - -- 2000 < - - -- TABLE 2 FIRE FLOW Ordinary Construction (ground area in square feet) US 1 2 3 4 500 < - - -- 13.900 - - -- 7,000 - -- 4,600 - - -- 2,800 - - -- 2 563 < - - -- 17,400 - - -- 8,700 - - -- 5,800 - - -- 4,400 - - -- 3 625 < - - -- 21,300 - - -- 10,700 - - -- 7,100: - -- 5,300 - - -- 4 688 < - - -- 25,500 - - -- 12,800 - - -- 8,500 - - -- 6,400 - - -- 5 750 < - - -- 30,100 - - -- 15,100 - - -- 10,000 - - -- 7,500 - - -- 6 813 < - - -- 35,200 - - -- 17,600 - - -- 11,700 - - -- 8,800 - - -- 7 875 <-- -- 40, 600 - - -- 20,300 - - -- 13,500 - - -- 10,200 - - -- 8 938 < - - -- 46, 400 - - -- 23,200 - - -- 15,500 - - -- 11,600 - - -- 9 1000 < - - -- 52, 500 - - -- 26:300 - - -- 17,500 - - -- 13,100 - - - -10 1063 < - - -- 59,100 - - - -29 ,600 - - -- 19,700 - - -- 14,800 - - - -11 1125 < -- -- 66, 000 - - -- 33,000 - - -- 22,000 - - -- 16,500 - - - -13 1188 < - - -- 73, 300 - - -- 36,700 - - -- 24,400 - - -- 18,300 - - - -14 1250 - . 81. 100 ---- 40 .600 ---- 27.0o0 ---- 20_lo0 ---- 16 ORDINANCE -5- date drafted 10/15/87 2 200 - - -- 11,000 700 - - -- 12,200 200 - - -- 13,500 00 1 2 3 4 5 6 7 8 9 10 11 12' 13. 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 TABLE 3 FIRE FLOW Non - combustible Construction round area in square feet) gpm 1 2 3 4 5 6 Stories 500 < - - -- 2 17,000 800 - - -- 10,900 - - -- 7,300 - - -- 5,500 - - -- 4,400 - - -- 3,600 563 < - - -- 27,200 - - -- 13,600 - - -- 9,100 - - -- 6,800 - - -- 5,400 - - -- 4,500 625 < - - -- 33,200 - - -- 16,600 - - -- 11,100 - - -- 8,300 - - -- 6,600 - - -- 5,500 750 688 < 39,700 - - -- 19,900 - - -- 13,200 - - -- 9,900 - - -- 7,900 - - -- 6,600 813 < < - - -- 47,100 - - -- 23,600 - - -- 15,700 - - -- 11,800 - - -- 9,400 - - -- 7,900 875 < ___ 813 _ 54,900- - - -27, 500 - - -- 18,300 --. -- 13,700 - - -- 11,000 - - -- 9,200 63, 400- - - -31, 700- - - -21, 100 - - -- 15,900 - - -- 12,700 - - -- 10,600 938 < - - -- 72,400- - - -36, 200- - - -24, 000 - - -- 18,100 - - -- 14,500 - - -- 12,100 1000 < - - -- 82,100- - - -41, 200- - - -27, 400 - - -- 20,500 - - -- 16,400 - - -- 13,700 1063 < - - -- 92,400- - - -46, 200- - - -30, 800 - - -- 23,100 - - -- 18,500 - - -- 15,400 TABLE 4 FIRE FLOW Fire Resistive Construction (ground area in square feet) 500 < ---- '.,,._.,,, - -- -- -- -- •vvv ---- 563 <---- 38,700 - - -- 19,400 - - -- 12,900 - - -- 9,700 - - -- 7,700 - - -- 6,500 625 < - - -- 48.300 - - -- 24,200 - - -- 16,100 - - -- 12,100 - - -- 9,700 - - -- 8,100 688 < - - -- 59, 000- - - -29, 500 - - -- 19,700 - - -- 14,800 - - -- 11,800 - - -- 9,800 70, 900 - - -- 35,500- - - -23, 600 - - -- 17,700 - - -- 14,200 - - -- 11,800 750 < - -- 83, 700 - - -- 41,900- - - -27, 900 - - -- 20,900 - - -- 16,800 - - -- 13,900 Section 15.18.040 Authority to Adjust Fire Flow Value The fire marshal shall have the authority to make adJustments to the fire flow values obtained from tables 1 through 4 in accordance with the following: A. The fire flow values obtained from the tables may be reduced up to 25% for occupancies having a low fire hazard or may be increased up to 25% for occupancies having a high fire hazard. The Appendix to the I.S.O. guide may be used to determine low or high hazard occupancies. The Fire Marshal shall exercise good Judgement in determining the hazard for occu- pancies not specifically mentioned. For lumber ORDINANCE -6- date drafted 10/15/87 i yards, petroleum storage, refineries, grain eleva- tors, and large chemical plants, where the number obtained from the table is a minimum value, the Fire Marshal shall increase the fire flow value obtained from the Tables by 25 %. The fire flow calculated shall not be less than 1000 gpm. 1 B. The fire flow values obtained from the tables may be reduced by the Fire Marshal up to 50% for complete 2 systematic sprinkler protection. Where the buildings are either fire resistive or non - combustible con - 3 struction,and have a low fire hazard, the reduction may be up to 75 %. The percentage reduction made for 4 an automatic sprinkler system will depend upon the extent to which the system is judged to reduce the 5 possibility of fire spreading within and beyond the fire area. Normally this reduction will not be the 6 maximum allowed without proper system supervision, including water flow and valves. The fire flow shall 7 not be less than 1000 gpm. 8 C. To the fire flow values obtained from the tables a. percentage shall be added for structures exposed 9 within 150 feet of the new structure or addition. This percentage shall depend upon the height, area 10 and construction of the building(s) being exposed, the separation, openings in the exposed building(s), 11 the length of the exposure, the provision of auto- matic sprinklers and /or outside sprinklers in the 12 building(s) exposed, the occupancy of the exposed building(s), and the effect of hillside locations on 13 the possible spread of fire. An unpierced perimeter wall may warrant up to a 10% exposure change. 14 The percentage for any one side generally shall not 15 exceed the following limits for the separations shown: 16 Separation Percentage 17 0 -10 feet 25% 18 11 -30 feet �qi 31 -60 feet 15 19 61 -100 feet 10 101 -150 feet 5 20 The total percentage shall be the sum of the percent - 21 ages for all sides, but shall not exceed 75 %. 22 D. The values obtain in A above is reduced by the percentage (if any) determined in B above and 23 increased by the percentage (if any) determined in C above. 24 E. In determining percentage increase and decrease in 25 fire flow, the Fire Marshal shall give consideration to the configuration of the building(s) and to the 26 Fire Department accessibility. 27 F. High one -story buildings: When a building is stated 28 at 1, 2, or more stories, the number of stories to be used in the formula depends upon the use being made 29 of the building. 30 For example, consider a 1 - 3 -story building. If the building is being used for high -piled stock, or for 31 ORDINANCE -7- 32 date drafted 10/15/87 1 2 3 4 5 6 7 8 9 10 11 12 13. 14 15 16 17 18 . 19 20 21 22 23 24 25 26 27 28 29 30 31 32 rack storage, the building would probably be consid- ered as 3 stories and, in addition, an increased percentage for occupancy may be warranted. However, if the building is being used for steel fabrication and the extra height is provided only to facilitate movement of ob9ects by a crane, the building would probably be considered as a 1 -story building and a decreased percentage for occupancy may be warranted. G. Where wood shingle roofs could contribute to spread- ing fires, add 500 gpm. Section 15.18.050 Exemptions The following new construction shall be exempt from the fire flow requirements set forth in this chapter: A. New Structures 11 Single- Family Residences Agriculture Buildings Farm buildings such as livestock and poultry buildings, milking barns, loafing sheds, farm equipment storage buildings relating to the preceding buildings, and similar use structures accessory to farming activities, provided . that these structures shall not be _a lace of human habitation or a place of employment where agricul- tural products are processed, treated or packaged: nor shall it be a place used by the public; and provided further that this exemption shall only apply to structures that are set back a minimum distance of 100 feet from the side and rear property line. Buildings, as example, which do not fall into Farm Buildings are: potato warehouses, granaries, mushroom growing buildings, commercial greenhouses, retail sales.dairies,.and other like use structures. 31 Other Structures and Buildings not previously exempted which are 2,500 sq. ft. or less in area; PROVIDED, that this exemption shall not apply to structures or buildings which will be used for Group H occupancies. B. Alterations and Additions to Existing Structures ORDINANCE -8- date drafted 10115/87 1) Alterations and additions to existing buildings or structures where the building or structure is otherwise exempt: PROVIDED, that the alteration does not remove the building or structure from exempt status. 2) Alterations or additions to existing buildings or structures where the building or structure is not exempt; when the alteration is less than a sub- stantial alteration as defined by this chapter ^or the alteration or addition will result in a building or structure that complies with one or more of the other fire flow exemptions: PROVIDED, that alterations or 1 2 3 4 5 6 7 8 9 10 11 12 13. 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 used for Group H 000upancy shall not be exempt. Section 15.18.060 Fire Hydrant Standard The following installation standards shall apply to fire hydrant installations providing required fire flow. A. Fire Hydrant Design Criteria 1) Fire hydrants shall have a minimum six (6) inch barrel, shall have a minimum of two 2 1/2 inch outlets and one 4 inch minimum inside diameter pumper port. 2) All hydrant connections shall have threads compati ble with those used by the local fire department. 3) Fire hydrants shall be self - draining and frost- free. 4) Fire hydrants shall meet American Waterworks Association standards and any additional speci fioations required by the local water surveyor. 5) Fire hydrants shall be provided with an auxiliary gate valve, installed to permit the repair and /or replacement of the fire hydrant without disruption of water service. 6) Flush -type hydrants are prohibited, except upon speoific approval of the Fire Marshal. 7) All hydrants shall be subject to testing by the local fire department and the Fire Marshal. The water purveyor shall be notified prior to any such testing. Testing shall be done in cooperation with such puryeyo- rs. B. Installation Criteria 1) Fire hydrants and water mains shall be installed to meet sound engineering practices as speoified by the Fire Marshal. based on applicable ciroumstanoes. The Fire Marshal shall make applications and plans availa- ble for comment by the local fire department. Fire hydrants shall be accessible to fire department pumpers over roads capable of supporting suoh vehicles. ORDINANCE -9- date drafted 10/15/87 and on the control valve. 1 2 3 4 5 6 7 8 9 10 11 12 13. 14 15 16 17 . 18 19 20 21 22' 23 24 25 26 27 28 29 30 31 32 (50) feet from build: of the Fire Marshal. Fire Marshal. vegetation nor shall the visibility of the hydrant be impaired for a distance of fifty (50) feet in the direction of vehicular approach to the fire hydrant. 7) Fire hydrants shall, when possible, be located at street intersections. 8) 'The location and design of all water mains. fire C. Number of Fire hydrants unless otherwise approved by the Fire Marshal. ha within one hundred fiftv (150) feet of each fire) went pumper connections. 5) If the reauired fire Section 15.18:070 Water Supply ORDINANCE -10- date drafted 10/15/87 1 2 3 4 5 6 7 8 9 10 11 12 13. 14 15 16 17 18 19 20 21 22 23 24 25 26 . 27 28 29 30 31 32 A. Ponds 1) Capacity through 1D. weather conditions. suotion inlet. 4) Pond to.be gunite lined or equivalent. 5) Proper sized line to be connected from standard type.hydrant into pond. 6) Minimum line size to hydrant is six (6) inch unless line is in excess of fifty (50) feet in length. If over fifty (50) feet, line size shall be no less than eight (8) inches. 7) Hydrant threads to be determined and approved by District Fire Chief. 8) Hydrant to be within three hundred (30 0) feet of furthest point of building being served. 9) Access road to hydrant must comply with Uniform Fire Code Section 10.207 (a). 10) Line to hydrant must be filled with water and pressurized. Minimum flow acceptable will be 500 gpm at 20 psi, 11) Pump on system to be automatic start based on drop in pressure on system. 12) Electrical service for pump separate from building. 13) Pump capacity shall not be less than required fire flow G.P.M. B. Reservoirs 1) Capacity to be determined by Tables 1A through 1D, and multiplied by 120 for industrial, to determine total reservoir capacity, and multiplied by 60 for all other complexes, to determine total reservoir capacity. 2.) Hydrant to be located within 100 feet of reservoir, and.. reservoir to be within 300 feet of furthest point of building being served. 3) Hydrant to be connected to reservoir with a line no less than eight (8) inches in diameter. Line to.meet Amerioan Waterworks Association Standards. ORDINANCE -11- date drafted -10 /15/87 5) Reservoir to be provided with a three (3) foot by three foot sump with line to hydrant connected to the, bottom of sump. v1 n. �' / fd . L � �r F y �: I� F• V, n 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 ORDINANCE.-12- date drafted 10/15/87 6 A gate valve to be installed between hydrant and reservoir. Reservoir to be connected to a minimum /4 inch line with automatic fill provisions, from either a domestic system, or a well system. 8 Reservoir to be provided with access opening large enough to provide entry. 9) Reservoir to be provided with a minimum of four (4) inch vent. 10) All vents and overflow openings in reservoir to be screened. 11) Reservoir to be constructed so that water level in reservoir, when full to capacity, is a minimum of 4 1/2 feet above steamer port of the hydrant. 12) Hydrant threads to be determined and approved by the applicable District Fire Chief. 13) Access road to hydrant must comply with Uniform Building Code Section 10.207(a). 14) All lines are to be insulated as required to prevent from freezing. 15) water supply to be provided with adequate vacuum break or backflow. 16) Plans of reservoir to be submitted and approved by Fire District and Fire Marshal prior to beginning construction. 17) Reservoir -to be complete and operational before building construction begins. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32. Section 15.18.080 Fire Marshal Authority Nothing in this chapter shall be construed so as to prevent the Fire Marshal from exercising the authority granted by Section 2.301 of the TT..: i•e...... DJ .... /....i ... ......... .i...i 41nw4 r.w4: F: e.wF:e... ... .,..:4 :..n ehwl7 i.e. to Section 2.301 where such modification results in a reduction in fire flow below the standards set forth in this chapter. The date of the letter of notification shall be deemed to be the date of the administrative decision. APPROVED this 15th day of OCTOBER , 1987 ATTEST: Carol Ebergson Z Clerk of the Council APPROVED AS TO FORM: WHATCOM COUNTY COUNCIL WHATCOM COUNTY, WASHINGTON WILLIAM P. ROEHL VICE CHAIRMAN (� APPROVED ( ) VETOED bL SHIPLEY VAN 1ANTEN County Executive Date: OCTOBER 16, 1987 Randall J. Watts, Chief Civil Deputy Prosecuting Attorney Published on 9/9/87 and 10/21/87 This ordinance becomes effective on OCTOBER 26, 1987 ORDINANCE -13- date drafted 10/15/87